AC Faults
AC Gas Leak in London & the M25
Refrigerant leaks reduce performance, raise energy use and release greenhouse gases. Finding the leak point is the key step; once found, the repair method depends on where it is and what it is made of.
What to do when you suspect an AC gas leak
Refrigerant leaks are usually slow and are not a gas-supply emergency, but switch the system off if you see oil staining, ice on pipework or hear hissing. Do not use naked flames near the unit. Note how long cooling has been poor and whether the system was recently worked on; leaks often appear at joints made during installation or alteration.
Repairing the leak
A flare can often be remade; a brazed joint repaired after recovering refrigerant; a corroded coil may need replacing. The repair is followed by a pressure test, evacuation and a weighed charge.
Leak checks under the F-Gas rules
Systems with 5 tonnes CO₂ equivalent or more need periodic leak checks: every 12 months from 5 t, every 6 months from 50 t and every 3 months from 500 t, halved in frequency where a working leak detection system is fitted. After a repair a further check is due within one month.
Other guides on refrigerant leak detection and repair
Refrigerant leak detection and repair: questions
Choosing the right visit
Describe the equipment and what you need — a repair, a service, an inspection or a quote for new equipment — so the visit is scoped correctly and the right engineer attends.
- The outcome you need from the visit
- Equipment details and access
- How findings will be reported
Engineer labour is £120 + VAT per hour with a one-hour minimum; parts and materials are quoted in writing before they are fitted.
How each type of visit works and all rates · What to have ready when you book · How we work